According to the
National Electric Code, section
690.15, PV arrays must have
a disconnecting means to
isolate the inverter from the
PV power source. Grid-tie
inverters that utilize PV arrays
with voltages above 250VDC
require a disconnect rated for
600VDC to perform this
function.
The Square-D 600 VDC
30 amp 3-pole safety switches
are UL listed to handle 13A at
600VDC per pole. They can
be used for disconnecting up
to three PV arrays for three
grid-tie inverters. It has
wiring lugs that are rated to
accept two #14 to #10 wires
in each lug. This allows the
disconnect switch to also act
as a string combiner in
systems that utilize two
strings of PV modules per
inverter. All other Square D
600 VDC disconnects are
rated for disconecting one
string at full rated
power.
Many
utilities require an AC
disconnect between an intertie
inverter and the AC load
center, close to the AC
service entrance, with a
visible and lockable handle. A
30 amp 240 volt disconnect is
good for up to 5kW at 240
VAC (one or two 2500W
intertie inverters) and the 60
amp disconnect is good for up
to 12.5kW (three to five
2500W intertie inverters). For
connection of multiple
inverters to one of these
disconnects, use an AC load
center, with a circuit breaker
for each inverter installed, as
an AC combiner box between
the inverters and the
disconnect switch. The
breakers can be back-fed with
the inverter outputs and the
load center main lugs will
handle the combined outputs
to be connected to the AC
disconnect.
Use Class-R fuses of the
proper amperage for fused
disconnects. Disconnects are
raintight (NEMA 3R) for
outdoor use. Order the
neutral bus bar and ground
bus bar if you need to land
these conductors in the
disconnect switch box.
The new Combi-Switch was specially designed with installers in mind. It provides the code-required external DC disconnect and protection for the SB6000U inverter all in one small enclosure. The Combi-Switch allows for up to four PV strings to be...
Heavy-duty fused safety disconnect switches for indoor or outdoor use with external lockable switch handle. This disconnect can be used as a service disconnect for AC or DC systems rated to 600 volts.
Specifications
Wire lugs rated #14-6AWG....
Heavy-duty non-fused safety disconnect switches for indoor or outdoor use with external lockable switch handle. This disconnect can be used as a service disconnect for AC or DC systems rated to 600 volts.
Specifications
Wire lugs rated...
Many utilities require an AC disconnect between an intertie inverter and the AC load center, close to the AC service entrance, with a visible and lockable handle. A 30 amp 240 volt disconnect is good for up to 5kW at 240 VAC (one or two 2500W...
Many utilities require an AC disconnect between an intertie inverter and the AC load center, close to the AC service entrance, with a visible and lockable handle. A 60 amp 240 volt disconnect is good for up to 12.5kW at 240 VAC (three to...